Cable size calculator
Enter the design current, protective device and correction factors to get the minimum tabulated current-carrying capacity your cable needs, then check the cable you picked.
Choose In ≥ Ib, then the cable’s tabulated rating must satisfy It ≥ In ÷ (Ca × Cg × Ci × Cc). A 32 A MCB with a grouping factor of 0.8 and an ambient factor of 0.94 needs It ≥ 32 ÷ (0.94 × 0.8) = 42.6 A. Then check voltage drop and Zs for the size you choose.
✓ Pick a cable whose tabulated It is at least 32.0 A, then check voltage drop and Zs.
- Minimum tabulated It
- 32.0 A
- Ib ≤ In
- Yes (28 ≤ 32 A)
Working
- It ≥ In ÷ (Ca × Cg × Ci × Cc) = 32 ÷ (1 × 1 × 1 × 1) = 32.0 A.
Check before you rely on it: figures are calculated from the formulas and conductor data shown, following BS 7671:2018 as amended. Check critical values against the current edition of BS 7671, the manufacturer’s data and your scheme’s requirements. Competence and compliance remain with the user.
Reference table
| Circuit | Max Zs | Max length |
|---|---|---|
| B6 lighting, 1.5/1.0 | 7.28 Ω | 191 m |
| B16 radial, 2.5/1.5 | 2.73 Ω | 102 m |
| B20 radial, 2.5/1.5 | 2.19 Ω | 78 m |
| B32 radial, 4/1.5 | 1.37 Ω | 51 m |
| B32 cooker, 6/2.5 | 1.37 Ω | 81 m |
| B40 shower, 10/4 | 1.09 Ω | 96 m |
The steps
- Design current Ib: the current the circuit will carry (after diversity).
- Protective device In: the next standard rating at or above Ib (Regulation 433.1.1: Ib ≤ In ≤ Iz).
- Correction factors from Appendix 4 of BS 7671: Ca for ambient temperature, Cg for grouping with other circuits, Ci for thermal insulation and Cc = 0.725 for a BS 3036 rewireable fuse (otherwise 1). Use 1 for any factor that does not apply.
- Minimum tabulated rating: It ≥ In ÷ (Ca × Cg × Ci × Cc). Pick a cable whose tabulated current-carrying capacity for your installation method is at least this.
- Check voltage drop and earth fault loop impedance for that size and length. Increase the size if either fails.
Why you enter It yourself
Current-carrying capacities depend on the cable type and installation method (clipped direct, in conduit, in an insulated wall and so on) and are tabulated in BS 7671 Appendix 4 and in manufacturers’ data. Read It for your cable and method from the table you use and enter it here; the calculator does the arithmetic and the checks.
Worked example
- Electric shower, 9.5 kW: Ib = 9500 ÷ 230 = 41.3 A, so In = 45 A or 50 A (here: 50 A).
- Clipped direct, no grouping, 30 °C ambient, no insulation: all factors 1, so It ≥ 50 A.
- 10 mm² twin and earth meets this in most installation methods; then check voltage drop (10 mm², 41.3 A, 15 m: 4.39 × 41.3 × 15 ÷ 1000 = 2.72 V, 1.18 %) and Zs for a B50 (max 0.87 Ω).
Writing certificates every week? Pro is £39/month ex VAT
- Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
- Your logo, company, accreditation and signature on every PDF
- History with search, copy and re-issue
- Renewal reminders in the app and in your calendar
- No “Free version” mark
Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.
Frequently asked questions
What do Ib, In, It and Iz mean?
Ib is the design current, In the rating of the protective device, It the tabulated current-carrying capacity of the cable for the installation method, and Iz the actual capacity after correction factors (It × Ca × Cg × Ci). The rule is Ib ≤ In ≤ Iz.
Why 0.725 for rewireable fuses?
A BS 3036 semi-enclosed fuse needs a larger overload before it operates, so the cable must be derated to protect it against overload. Dividing by 0.725 increases the required It accordingly.
Does the calculator choose the cable for me?
It gives the minimum tabulated rating and checks the cable you choose. Selecting the size from the current-carrying capacity table for your installation method is up to you, as is checking voltage drop, Zs and the adiabatic equation for the cpc.
Can I rely on these figures?
They are calculated from the formulas and conductor data stated on the page, and the working is shown so you can check it. They are a design and testing aid, not a substitute for BS 7671:2018 as amended, the manufacturer’s data or your competent person scheme’s requirements. Check critical values against the current edition before you sign anything.