Zs calculator (earth fault loop impedance)

Enter Ze and R1 + R2 to get Zs, the prospective earth fault current and a pass or fail against the maximum Zs for the protective device.

Zs = Ze + (R1 + R2). With Ze = 0.35 Ω and R1 + R2 = 0.39 Ω, Zs = 0.74 Ω and the earth fault current is 230 ÷ 0.74 = 311 A. A B32 allows 1.37 Ω (80 % = 1.09 Ω), so the circuit passes.

Updated · BS 7671:2018 as amended · check against BS 7671 and your scheme

✓ 0.74 Ω is within the 1.09 Ω limit for a B32.

Zs = Ze + (R1 + R2)
0.74 Ω
Prospective earth fault current
311 A
Maximum Zs for B32
1.37 Ω
80 % test-reading limit
1.09 Ω
Working
  1. Zs = 0.35 + 0.39 = 0.74 Ω.
  2. If = U0 ÷ Zs = 230 ÷ 0.74 = 311 A.
  3. Max Zs = 0.95 × 230 ÷ (5 × 32) = 1.366 Ω; × 0.8 = 1.09 Ω.

Check before you rely on it: figures are calculated from the formulas and conductor data shown, following BS 7671:2018 as amended. Check critical values against the current edition of BS 7671, the manufacturer’s data and your scheme’s requirements. Competence and compliance remain with the user.

Reference table

Longest run that keeps Zs within the maximum, with Ze = 0.35 Ω (typical TN-C-S) and conductors at 70 °C. Voltage drop may limit the run first.
CircuitMax ZsMax length
B6 lighting, 1.5/1.07.28 Ω191 m
B16 radial, 2.5/1.52.73 Ω102 m
B20 radial, 2.5/1.52.19 Ω78 m
B32 radial, 4/1.51.37 Ω51 m
B32 cooker, 6/2.51.37 Ω81 m
B40 shower, 10/41.09 Ω96 m

The earth fault loop

When a line conductor touches earthed metalwork, fault current flows from the transformer winding, through the line conductor to the fault, back through the circuit protective conductor, the main earthing terminal and the supplier’s earth path to the transformer. Zs is the impedance of that whole loop.

Ze is the part outside the installation (measured at the origin with the main earthing conductor disconnected, then reconnected). R1 + R2 is the resistance of the circuit’s line and protective conductors, measured with a continuity test or calculated from the cable size and length.

Worked example

  1. Ze measured at the origin: 0.35 Ω (TN-C-S).
  2. R1 + R2 for 20 m of 2.5/1.5 mm² twin and earth: 20 × 19.51 ÷ 1000 = 0.39 Ω.
  3. Zs = 0.35 + 0.39 = 0.74 Ω.
  4. Prospective earth fault current = 230 ÷ 0.74 = 311 A.
  5. B32 maximum Zs = 0.95 × 230 ÷ 160 = 1.37 Ω; 80 % = 1.09 Ω. 0.74 Ω is within it.

If Zs is too high

  • Check for a loose or high-resistance connection first: compare the measured R1 + R2 with the calculated value.
  • Use a larger protective conductor or a shorter route.
  • Use a lower rating or a type B instead of type C device, if the load allows.
  • Where Zs cannot be brought within the limit for the overcurrent device, an RCD can provide fault protection, subject to the conditions in BS 7671.

Writing certificates every week? Pro is £39/month ex VAT

  • Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
  • Your logo, company, accreditation and signature on every PDF
  • History with search, copy and re-issue
  • Renewal reminders in the app and in your calendar
  • No “Free version” mark

Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.

See plans

Frequently asked questions

What is the difference between Ze and Zs?

Ze is the external earth fault loop impedance at the origin of the installation. Zs is the total at a point on a circuit: Ze plus the circuit’s R1 + R2.

Should I compare my reading with the full maximum or 80 %?

Readings are taken at room temperature, but the maximum assumes conductors at full load temperature, when their resistance is about 20 % higher. Comparing the reading with 80 % of the maximum allows for that.

How is prospective fault current calculated?

Divide the nominal voltage to earth by the loop impedance: If = 230 ÷ Zs. Record the highest prospective fault current (Ipf) at the origin on the certificate; the protective devices must be able to break it.

Can I rely on these figures?

They are calculated from the formulas and conductor data stated on the page, and the working is shown so you can check it. They are a design and testing aid, not a substitute for BS 7671:2018 as amended, the manufacturer’s data or your competent person scheme’s requirements. Check critical values against the current edition before you sign anything.