Gas rate calculator
Time the meter with only the appliance running at full rate, enter the gas used and the time, and get the gas rate and heat input in kW gross and net, with the working shown.
Gas rate (m³/h) = gas used (m³) × 3600 ÷ seconds. Heat input (kW gross) = m³/h × calorific value (MJ/m³) ÷ 3.6, and net ≈ gross ÷ 1.11 for natural gas. For example 0.04 m³ in 2 minutes is 1.2 m³/h, 12.90 kW gross and 11.62 kW net.
- Gas rate
- 1.200 m³/h
- Heat input, gross
- 12.90 kW
- Heat input, net
- 11.62 kW
Working
- 0.04 m³ × 3600 ÷ 120 s = 1.200 m³/h.
- Gross input = 1.200 m³/h × 38.7 MJ/m³ (natural gas) ÷ 3.6 = 12.90 kW.
- Net input = 12.90 ÷ 1.11 = 11.62 kW.
Gas Safe registered engineers only: work on gas appliances and installations must be carried out by a Gas Safe registered engineer competent for the work. Figures come from the formulas and assumptions shown; the manufacturer’s instructions, the current British Standards and IGEM procedures take precedence. Competence and compliance remain with the user. Not affiliated with Gas Safe Register. Not legal advice.
Reference table
| kW gross | m³/h | m³ in 2 minutes | 1 ft³ dial (s) |
|---|---|---|---|
| 6 kW | 0.558 | 0.019 | 183 |
| 9 kW | 0.837 | 0.028 | 122 |
| 12 kW | 1.116 | 0.037 | 91 |
| 15 kW | 1.395 | 0.047 | 73 |
| 18 kW | 1.674 | 0.056 | 61 |
| 24 kW | 2.233 | 0.074 | 46 |
| 30 kW | 2.791 | 0.093 | 37 |
| 35 kW | 3.256 | 0.109 | 31 |
How to gas rate an appliance
- Turn off every other gas appliance in the property.
- Run the appliance at its maximum rate (for a combi, hot water at full flow) and let it settle for a few minutes.
- Metric meter: note the reading, wait exactly two minutes and note it again. The difference is the gas used.
- Imperial meter: time one full revolution of the test dial.
- Enter the figures above and compare the result with the data plate, using the same basis (gross or net).
Gross and net heat input
Gross (Hs) includes the heat in the water vapour produced by burning the gas; net (Hi) leaves it out. Most current appliances show net heat input on the data plate. For natural gas the gross figure is about 11 % higher than net (× 1.11); for LPG about 9 %.
The calorific value of natural gas in Great Britain is usually between about 38 and 40 MJ/m³. The calculator uses 38.7 MJ/m³ by default; choose “Enter calorific value” to use the figure on a recent bill.
Worked examples
- Metric: 0.04 m³ in 120 s = 1.200 m³/h → 1.2 × 38.7 ÷ 3.6 = 12.90 kW gross → 11.62 kW net.
- Imperial: 1 ft³ dial in 60 s = 60 ft³/h = 1.699 m³/h → 18.26 kW gross → 16.45 kW net.
- Combi rated 24 kW net: 0.08 m³ in 120 s = 2.400 m³/h → 25.80 kW gross → 23.24 kW net, 3.2 % under the rating.
Writing certificates every week? Pro is £39/month ex VAT
- Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
- Your logo, company, accreditation and signature on every PDF
- History with search, copy and re-issue
- Renewal reminders in the app and in your calendar
- No “Free version” mark
Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.
Frequently asked questions
What tolerance is acceptable?
Check the manufacturer’s instructions for the appliance. The calculator flags anything more than 5 % from the rated input so you look again at the burner pressure and the injector.
Why is my gas rate low?
Common causes are low working pressure at the meter or appliance, a partly blocked injector or filter, undersized pipework, another appliance running during the test, or the appliance not yet at full rate.
Does this work for LPG?
Yes, choose LPG propane (CV 93.1 MJ/m³) and time the LPG meter the same way.
How accurate are these figures?
They come from the formulas shown on the page and the stated assumptions (for example a calorific value of 38.7 MJ/m³ for natural gas). The manufacturer’s instructions, the current British Standards and IGEM procedures take precedence. Gas work must be done by a Gas Safe registered engineer.