Max Zs values: table and calculator
Pick the protective device to get its maximum earth fault loop impedance, the 80 % figure to compare with your test reading, and the working.
Maximum Zs = 0.95 × 230 V ÷ Ia (Regulation 411.4.4). For a type B MCB Ia is 5 × In, so a B32 allows 1.37 Ω, a B16 2.73 Ω and a B6 7.28 Ω. Type C uses 10 × In (C32: 0.68 Ω) and type D 20 × In (D32: 0.34 Ω). Compare a cold test reading with 80 % of the maximum (B32: 1.09 Ω).
- Disconnection current Ia
- 160 A
- Maximum Zs
- 1.37 Ω
- 80 % value to compare with a test reading
- 1.09 Ω
Working
- Ia = 5 × 32 A = 160 A.
- Zs ≤ Cmin × U0 ÷ Ia = 0.95 × 230 V ÷ 160 A = 1.366 Ω → 1.37 Ω.
- A reading taken cold is lower than at full load, so compare it with 80 %: 1.366 × 0.8 = 1.09 Ω.
Check before you rely on it: figures are calculated from the formulas and conductor data shown, following BS 7671:2018 as amended. Check critical values against the current edition of BS 7671, the manufacturer’s data and your scheme’s requirements. Competence and compliance remain with the user.
Reference table
| Rating | Type B | B × 0.8 | Type C | C × 0.8 | Type D | D × 0.8 |
|---|---|---|---|---|---|---|
| 3 A | 14.57 | 11.65 | 7.28 | 5.83 | 3.64 | 2.91 |
| 6 A | 7.28 | 5.83 | 3.64 | 2.91 | 1.82 | 1.46 |
| 10 A | 4.37 | 3.50 | 2.19 | 1.75 | 1.09 | 0.87 |
| 16 A | 2.73 | 2.19 | 1.37 | 1.09 | 0.68 | 0.55 |
| 20 A | 2.19 | 1.75 | 1.09 | 0.87 | 0.55 | 0.44 |
| 25 A | 1.75 | 1.40 | 0.87 | 0.70 | 0.44 | 0.35 |
| 32 A | 1.37 | 1.09 | 0.68 | 0.55 | 0.34 | 0.27 |
| 40 A | 1.09 | 0.87 | 0.55 | 0.44 | 0.27 | 0.22 |
| 50 A | 0.87 | 0.70 | 0.44 | 0.35 | 0.22 | 0.17 |
| 63 A | 0.69 | 0.55 | 0.35 | 0.28 | 0.17 | 0.14 |
| 80 A | 0.55 | 0.44 | 0.27 | 0.22 | 0.14 | 0.11 |
| 100 A | 0.44 | 0.35 | 0.22 | 0.17 | 0.11 | 0.09 |
| 125 A | 0.35 | 0.28 | 0.17 | 0.14 | 0.09 | 0.07 |
| IΔn | Maximum Zs |
|---|---|
| 10 mA | 5000 Ω |
| 30 mA | 1667 Ω |
| 100 mA | 500 Ω |
| 300 mA | 167 Ω |
| 500 mA | 100 Ω |
How maximum Zs is worked out
For a TN system (TN-S or TN-C-S) the protective device must disconnect a fault between line and earth within the time in Table 41.1 of BS 7671: 0.4 s for 230 V final circuits up to 63 A, and 5 s for distribution circuits and final circuits over 63 A. Regulation 411.4.4 turns that into an impedance limit: Zs × Ia ≤ U0 × Cmin.
U0 is the nominal voltage to earth (230 V). Cmin is the minimum voltage factor, 0.95, which allows for the supply running low. Ia is the current that makes the device operate within the required time. For MCBs and RCBOs to BS EN 60898 and BS EN 61009, the instantaneous trip is at most 5 × In (type B), 10 × In (type C) or 20 × In (type D), so those multiples are used for Ia.
The tabulated maximum assumes the conductors are at their full operating temperature. A reading taken on a cold circuit is lower, so the usual check is that the measured Zs is no more than 80 % of the tabulated maximum.
Worked examples
- B32 ring final: Ia = 5 × 32 = 160 A. Max Zs = 0.95 × 230 ÷ 160 = 1.366 → 1.37 Ω. 80 % = 1.09 Ω.
- C20 radial: Ia = 10 × 20 = 200 A. Max Zs = 218.5 ÷ 200 = 1.09 Ω. 80 % = 0.87 Ω.
- D16 motor circuit: Ia = 20 × 16 = 320 A. Max Zs = 218.5 ÷ 320 = 0.68 Ω. 80 % = 0.55 Ω.
- TT installation with a 30 mA RCD providing fault protection: Zs ≤ 50 V ÷ 0.03 A = 1667 Ω (Regulation 411.5.3), but aim for 200 Ω or less so the reading stays stable.
Fuses and other devices
BS 88 and BS 3036 fuses do not have a fixed multiple of In: Ia comes from the device’s time/current characteristic at 0.4 s or 5 s. Choose “Other device” in the calculator and enter Ia from the curve; the same formula applies.
Typical maximum Ze from the supplier
- TN-C-S (PME): 0.35 Ω.
- TN-S (cable sheath earth): 0.8 Ω.
- TT: no supplier earth; Ze depends on your electrode. A value of 21 Ω is often quoted for a supplier’s TT figure, but your RA is what counts.
- These are typical figures quoted by distribution network operators for domestic supplies. Always measure Ze; use the quoted figure only for design before the supply exists.
Writing certificates every week? Pro is £39/month ex VAT
- Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
- Your logo, company, accreditation and signature on every PDF
- History with search, copy and re-issue
- Renewal reminders in the app and in your calendar
- No “Free version” mark
Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.
Frequently asked questions
What is the max Zs for a B32?
1.37 Ω (0.95 × 230 ÷ 160). Compare a measured reading with 80 % of that: 1.09 Ω.
What is the max Zs for a B6 lighting circuit?
7.28 Ω (0.95 × 230 ÷ 30). The 80 % test value is 5.83 Ω.
Why do older tables show different values?
Before the 18th Edition the tables used 230 V without the 0.95 Cmin factor, so the figures were about 5 % higher (for example 1.44 Ω for a B32). Values worked out with Cmin = 0.95 apply to BS 7671:2018 and its amendments.
Do RCBOs have the same max Zs as MCBs?
Yes for the overcurrent part: an RCBO with a type B curve has the same maximum Zs as a type B MCB of the same rating. Its residual current part also gives fault protection, which in a TT system is checked against 50 V ÷ IΔn.
What is Table 41.3?
The table in BS 7671 that lists maximum Zs for circuit-breakers and RCBOs at 0.4 s and 5 s. Its values come from the same formula used here, so this calculator gives the same result for MCBs and RCBOs. Fuse tables (41.2 and 41.4) depend on fuse curves.
Can I rely on these figures?
They are calculated from the formulas and conductor data stated on the page, and the working is shown so you can check it. They are a design and testing aid, not a substitute for BS 7671:2018 as amended, the manufacturer’s data or your competent person scheme’s requirements. Check critical values against the current edition before you sign anything.