F-gas leak check record and frequency calculator
Work out the CO2 equivalent of an air-conditioning, refrigeration or heat pump system and how often it must be leak checked, then keep the equipment record: refrigerant, charge, every leak check, gas added or recovered and the company and engineer certificate numbers.
Equipment holding 5 tonnes CO2 equivalent or more of F-gas must be leak checked: every 12 months from 5 t, every 6 months from 50 t and every 3 months from 500 t, with each interval doubled if a leak detection system is fitted. Tonnes CO2e = charge in kg × GWP ÷ 1000. Operators keep the records for at least five years.
- CO2 equivalent
- 25.06 t
- Leak checks
- At least every 12 months
- Leak detection system
- Not required
- Keep records for
- At least 5 years
Working
- 12 kg × GWP 2088 ÷ 1000 = 25.06 tonnes CO2 equivalent.
- Article 4(3): 5 to under 50 t → every 12 months.
- GWP values are the ones commonly quoted under the GB F-gas Regulation (IPCC AR4 basis). Use the figure on the equipment label if it differs.
Free PDFs carry a small “Free version” mark. Pro removes it, saves your certificates, adds your logo and company details and reminds you before renewals.
Important: this tool records the results and findings you enter and formats them as a document. It does not inspect, test or assess anything. Competence and compliance remain with the user. Not legal advice.
Reference table
| Refrigerant | GWP | 5 t (12 months) | 50 t (6 months) | 500 t (3 months) |
|---|---|---|---|---|
| R32 | 675 | 7.4 kg | 74.1 kg | 740.7 kg |
| R134a | 1430 | 3.5 kg | 35.0 kg | 349.7 kg |
| R404A | 3922 | 1.3 kg | 12.7 kg | 127.5 kg |
| R407A | 2107 | 2.4 kg | 23.7 kg | 237.3 kg |
| R407C | 1774 | 2.8 kg | 28.2 kg | 281.8 kg |
| R407F | 1825 | 2.7 kg | 27.4 kg | 274.0 kg |
| R410A | 2088 | 2.4 kg | 23.9 kg | 239.5 kg |
| R422D | 2729 | 1.8 kg | 18.3 kg | 183.2 kg |
| R448A | 1387 | 3.6 kg | 36.0 kg | 360.5 kg |
| R449A | 1397 | 3.6 kg | 35.8 kg | 357.9 kg |
| R452A | 2140 | 2.3 kg | 23.4 kg | 233.6 kg |
| R454B | 466 | 10.7 kg | 107.3 kg | 1073.0 kg |
| R513A | 631 | 7.9 kg | 79.2 kg | 792.4 kg |
Leak check frequency
Hermetically sealed equipment that is labelled as such and holds less than 10 t CO2e is exempt from leak checks. Leak checks on stationary refrigeration, air-conditioning, heat pumps and refrigerated truck units must be done by a person holding the appropriate F-gas certificate (Article 4(2)).
| F-gas in the equipment | Without leak detection | With leak detection | Leak detection system |
|---|---|---|---|
| Under 5 t CO2e | No leak checks | No leak checks | Not required |
| 5 t to under 50 t CO2e | At least every 12 months | At least every 24 months | Not required |
| 50 t to under 500 t CO2e | At least every 6 months | At least every 12 months | Not required |
| 500 t CO2e or more | At least every 3 months | At least every 6 months | Required, and checked at least every 12 months (Article 5) |
What the operator must record (Article 6)
For each piece of equipment that needs leak checks, the operator keeps the records below for at least five years, and the company doing the work keeps copies for five years too.
- Type and quantity of F-gas installed.
- Quantities added during installation, maintenance or servicing, or because of leakage.
- Whether recycled or reclaimed gas was used, with the name and address of the facility and its certificate number.
- Quantity recovered.
- The company that installed, serviced, maintained, repaired or decommissioned the equipment, with its certificate number.
- Dates and results of the leak checks.
- If decommissioned, how the gas was recovered and disposed of.
“F-gas certificate”: three different things
- Personal F-gas certificate: the engineer’s qualification to handle F-gas (for example a Category I certificate for refrigeration, air-conditioning and heat pumps).
- Company F-gas certificate: required for businesses that install, service, maintain, repair or decommission stationary equipment, issued by an approved certification body.
- Leak check record: the equipment log the operator keeps under Article 6. This page is that record; it does not replace either certificate.
Sources
- Regulation (EU) No 517/2014 on fluorinated greenhouse gases, as it applies in Great Britain, Articles 4, 5 and 6: legislation.gov.uk/eur/2014/517, read 18 November 2026.
- GOV.UK, F gas in refrigeration, air conditioning and fire protection systems: gov.uk/guidance/f-gas-in-refrigeration-air-conditioning-and-fire-protection-systems, read 18 November 2026.
- Northern Ireland follows the EU F-gas Regulation (EU) 2024/573, whose rules differ; check the current guidance if your equipment is there.
Writing certificates every week? Pro is £39/month ex VAT
- Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
- Your logo, company, accreditation and signature on every PDF
- History with search, copy and re-issue
- Renewal reminders in the app and in your calendar
- No “Free version” mark
Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.
Frequently asked questions
How do I work out tonnes CO2 equivalent?
Multiply the refrigerant charge in kg by the gas’s global warming potential (GWP) and divide by 1000. For example 12 kg of R410A (GWP 2088) is 12 × 2088 ÷ 1000 = 25.06 t CO2e, so it needs a leak check at least every 12 months.
Do split air-conditioning units need leak checks?
Only if the charge in the system reaches 5 t CO2e. A small R32 split with 1 kg (0.68 t) does not; an R410A system needs checks from about 2.4 kg. The calculator and the threshold table give the charge for each refrigerant.
Who is the operator?
The person or business that has actual control over the technical functioning of the equipment. It is usually the building owner or tenant who runs the system, not the maintenance contractor, unless the contract hands over that control.
Is this an official form?
No. There is no prescribed official form for this record. The law lists what the record must contain; this page uses our own layout and wording to cover that list. It is not issued, approved or accredited by HSE, any government department or any certification scheme.
Can I get a reminder before the next date?
Yes, with Pro or Business. Save the record to your account and its next due date appears in your due list and calendar feed. Business also shows it per property in the register.
Is anything I type uploaded?
Not unless you choose to save it. The form, the checker and the PDF run in your browser on your device, and a draft stays in your browser’s local storage. Only when you are signed in to a Pro or Business plan and press “Save to account” is the record stored on our server, where its next due date feeds your reminders.