Enter the load and the pipe run to check the pressure loss against the 1 mbar allowed between the meter and the appliance, and find the smallest copper pipe that keeps within it.

Add 0.5 m for every elbow or tee and 0.3 m for every bend to the measured length. Then pressure loss (mbar) = 0.6 × L × (Q ÷ 0.0071)² ÷ d⁵, with Q in m³/h and d the bore in mm. A 30 kW load (2.79 m³/h) through 22 mm copper over 10 m with two elbows and a tee loses about 0.32 mbar.

Updated · Gas Safety (Installation and Use) Regulations 1998 · Gas Safe registered engineers only

✓ 22 mm is large enough: 0.32 mbar is within 1 mbar.

Gas rate
2.79 m³/h
Effective length
11.5 m
Pressure loss
0.32 mbar
Pipe capacity at 1 mbar
4.96 m³/h
Smallest copper size within the limit
22 mm
Working
  1. Gas rate = 30 kW × 3.6 ÷ 38.7 MJ/m³ = 2.791 m³/h.
  2. Effective length = 10 m + 2 × 0.5 + 1 × 0.5 + 0 × 0.3 = 11.5 m.
  3. Pressure loss (Pole’s formula) = s × L × (Q ÷ 0.0071)² ÷ d⁵ = 0.6 × 11.5 × (2.791 ÷ 0.0071)² ÷ 20.2⁵ = 0.317 mbar (d = 20.2 mm bore).
  4. Capacity at 1 mbar = 0.0071 × √(1 × 20.2⁵ ÷ (0.6 × 11.5)) = 4.96 m³/h.

Gas Safe registered engineers only: work on gas appliances and installations must be carried out by a Gas Safe registered engineer competent for the work. Figures come from the formulas and assumptions shown; the manufacturer’s instructions, the current British Standards and IGEM procedures take precedence. Competence and compliance remain with the user. Not affiliated with Gas Safe Register. Not legal advice.

Reference table

Approximate natural gas capacity (m³/h) of straight copper pipe for a 1 mbar loss, from Pole’s formula (Q = 0.0071 √(h d⁵ ÷ s L), s = 0.6). Add 0.5 m per elbow or tee and 0.3 m per bend to the length. Check against BS 6891 and the pipe manufacturer’s tables.
Pipe3 m6 m9 m12 m15 m20 m
15 mm3.62.62.11.81.61.4
22 mm9.76.95.64.94.33.8
28 mm18.613.110.79.38.37.2
35 mm32.122.718.516.114.412.4

How to size gas pipework

  1. Add up the maximum heat input of every appliance the section supplies and convert it to m³/h (kW × 3.6 ÷ 38.7 for natural gas).
  2. Measure the pipe length from the meter (or the previous branch) to the appliance.
  3. Count the fittings and add their equivalent length.
  4. Check the loss for each section. The total from the meter outlet to any appliance inlet should not be more than 1 mbar at full load.

About Pole’s formula

Pole’s formula, Q = 0.0071 √(h d⁵ ÷ s L), is the usual approximation for low-pressure natural gas (relative density s = 0.6). It tends to give slightly higher capacities than the published BS 6891 tables, especially for 15 mm pipe, so the calculator warns when a result is within 25 % of the limit. Use the BS 6891 tables or the pipe manufacturer’s data for the final design, and their equivalent lengths for other pipe materials.

Worked examples

  • 30 kW gross on 22 mm, 10 m with two elbows and a tee: L = 11.5 m, Q = 2.79 m³/h, loss = 0.32 mbar. Fine.
  • The same load on 15 mm: loss = 2.29 mbar. Too small.
  • 60 kW gross (5.58 m³/h) over 20 m: 22 mm loses 2.20 mbar, 28 mm 0.60 mbar, so 28 mm is the smallest that works.

Writing certificates every week? Pro is £39/month ex VAT

  • Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
  • Your logo, company, accreditation and signature on every PDF
  • History with search, copy and re-issue
  • Renewal reminders in the app and in your calendar
  • No “Free version” mark

Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.

See plans

Frequently asked questions

What is the maximum pressure drop for gas pipework?

For a domestic natural gas installation the usual design limit is 1 mbar between the meter outlet and the appliance inlet with all appliances at full rate.

Can I use this for LPG or plastic pipe?

No. It assumes natural gas in copper pipe. LPG systems and other pipe materials have different densities, pressures, bore sizes and fitting allowances.

How accurate are these figures?

They come from the formulas shown on the page and the stated assumptions (for example a calorific value of 38.7 MJ/m³ for natural gas). The manufacturer’s instructions, the current British Standards and IGEM procedures take precedence. Gas work must be done by a Gas Safe registered engineer.