TM44 air-conditioning inspection: due date checker
Find out whether your building’s air-conditioning needs an energy assessor’s inspection and when the next one is due, then keep a register of every unit, its output, refrigerant and leak check date, and the last inspection report reference.
In England and Wales, an air-conditioning system with a combined effective rated output of more than 12 kW must be inspected by an accredited energy assessor at intervals not exceeding five years. The first inspection is due within five years of the system first being put into service. The person who controls the system arranges it and keeps the latest report.
✗ Overdue by 265 days (was due 28/02/2026).
- Inspection required
- Yes (more than 12 kW)
- First inspection by
- 28/02/2026
- Who inspects
- An accredited energy assessor
Working
- Regulation 17: 24 kW is more than 12 kW, so the system must be inspected.
- Regulation 18(2)–(3)(a): first inspection before the last day of the five years beginning with the date first put into service (01/03/2021) → by 28/02/2026.
- The relevant person is whoever controls the operation of the system; they must keep the latest report (regulation 20).
Free PDFs carry a small “Free version” mark. Pro removes it, saves your certificates, adds your logo and company details and reminds you before renewals.
Important: this tool records the results and findings you enter and formats them as a document. It does not inspect, test or assess anything. Competence and compliance remain with the user. Not legal advice.
Does my air conditioning need a TM44 inspection?
| Question | Rule | Regulation |
|---|---|---|
| Which systems? | Effective rated output of more than 12 kW | 17(1) |
| Several units? | Units whose temperature the same person can control count as one system, so add their outputs | 17(2) |
| How often? | Accessible parts inspected at intervals not exceeding five years | 18(1) |
| First inspection? | Before the end of five years from the date first put into service (systems in service from 1 January 2008) | 18(2), 18(3)(a) |
| Older systems? | Over 250 kW: first inspection by 4 January 2009; over 12 kW: by 4 January 2011 | 18(3)(b) |
| Who is responsible? | The relevant person: whoever controls the operation of the system | 2(1), 18(1) |
| What to keep? | The most recent inspection report, passed on to any new relevant person | 20 |
What the inspection report covers
The energy assessor’s report assesses the efficiency of the system and whether it is sized for the cooling the building needs, with advice on improvements, replacement and alternatives, and whether the system can optimise its performance under typical operating conditions. It gives the register reference number, the building address, the assessor, their accreditation scheme and the inspection date (regulation 19). The report is lodged on the national register.
The register on this page is your own record of the system between inspections. It does not replace the assessor’s report.
TM44 and F-gas: two separate duties
The TM44 inspection is about energy efficiency, every five years. F-gas leak checks are about refrigerant leaks and run on a much shorter cycle, set by the CO2 equivalent of the charge. Most systems over 12 kW need both. Use the F-gas leak check calculator for the leak check interval of each unit.
Sources
- Energy Performance of Buildings (England and Wales) Regulations 2012 (SI 2012/3118), regulations 2, 17, 18, 19 and 20: legislation.gov.uk/uksi/2012/3118, read 18 November 2026.
- GOV.UK, Air conditioning inspections for buildings: gov.uk/government/publications/air-conditioning-inspections-for-buildings, read 18 November 2026.
- CIBSE TM44 Inspection of air conditioning systems: named as the method assessors use; buy it from CIBSE.
- Scotland and Northern Ireland have their own rules for air-conditioning inspections.
Writing certificates every week? Pro is £39/month ex VAT
- Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
- Your logo, company, accreditation and signature on every PDF
- History with search, copy and re-issue
- Renewal reminders in the app and in your calendar
- No “Free version” mark
Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.
Frequently asked questions
What is a TM44 certificate?
People usually mean the air-conditioning inspection report produced by an accredited energy assessor. TM44 is the name of the CIBSE guidance the assessor follows. There is no separate certificate: the report is the evidence that the inspection was done.
Who can carry out a TM44 inspection?
An energy assessor accredited for air-conditioning inspections through a government-approved accreditation scheme. The report states the scheme, and you can check the assessor on the national register.
Does a landlord or a tenant arrange the inspection?
Whoever controls the operation of the system. In a single-let building where the tenant runs the air conditioning, that is usually the tenant; for central plant run by the landlord, the landlord. Check the lease.
How do I find the effective rated output?
Use the rated cooling capacity on each unit’s data plate or in the manufacturer’s data, and add the units the same person controls. A building with three 7.1 kW splits has 21.3 kW and needs inspecting.
Can I get a reminder before the next date?
Yes, with Pro or Business. Save the record to your account and its next due date appears in your due list and calendar feed. Business also shows it per property in the register.
Is anything I type uploaded?
Not unless you choose to save it. The form, the checker and the PDF run in your browser on your device, and a draft stays in your browser’s local storage. Only when you are signed in to a Pro or Business plan and press “Save to account” is the record stored on our server, where its next due date feeds your reminders.