Gas ventilation calculator
Work out the free area of the permanent vents an appliance needs, from its net heat input and where it is installed. The reference table lists the compartment rates.
An open-flued appliance in a room needs a permanent vent of 5 cm² for every kW of net heat input above 7 kW: a 20 kW open-flued boiler needs (20 − 7) × 5 = 65 cm². Room-sealed appliances in a room need no vent; in a compartment they need high and low vents.
- Permanent vent to outside (free area)
- 65 cm²
Working
- 5 cm² for every kW of net input above 7 kW: (20 − 7) × 5 = 65 cm².
- Use the free area of the vent (marked on it), not its overall size. Where the manufacturer asks for more, use their figure.
Gas Safe registered engineers only: work on gas appliances and installations must be carried out by a Gas Safe registered engineer competent for the work. Figures come from the formulas and assumptions shown; the manufacturer’s instructions, the current British Standards and IGEM procedures take precedence. Competence and compliance remain with the user. Not affiliated with Gas Safe Register. Not legal advice.
Reference table
| Compartment | High level (cm²/kW) | Low level (cm²/kW) |
|---|---|---|
| Open-flued, vents to a room | 10 | 20 |
| Open-flued, vents to outside | 5 | 10 |
| Room-sealed, vents to a room | 10 | 10 |
| Room-sealed, vents to outside | 5 | 5 |
The usual rules for domestic natural gas (up to 70 kW)
- Open-flued in a room: 5 cm² per kW of net input above 7 kW, to outside.
- Open-flued in a compartment: high 10 and low 20 cm²/kW to a room, or high 5 and low 10 cm²/kW to outside. The room also needs its own vent.
- Room-sealed in a compartment: high and low 10 cm²/kW each to a room, or 5 cm²/kW each to outside.
- Flueless cooker: 100 cm² in a room under 5 m³, 50 cm² for 5 to 10 m³ (not needed with a door straight to outside), none over 10 m³; an openable window in every case.
Before you rely on it
These are the commonly applied rates from BS 5440-2 for domestic natural gas appliances. Where the manufacturer asks for more, use their figure. Gas fires, flueless water heaters, LPG appliances and installations with more than one open-flued appliance in the same space have their own rules. Use the free area marked on the vent, not its overall size.
Writing certificates every week? Pro is £39/month ex VAT
- Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
- Your logo, company, accreditation and signature on every PDF
- History with search, copy and re-issue
- Renewal reminders in the app and in your calendar
- No “Free version” mark
Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.
Frequently asked questions
Do room-sealed boilers need ventilation?
Not in a room. In a compartment or cupboard they need high- and low-level vents for cooling unless the manufacturer says otherwise.
Why the 7 kW allowance?
Normal adventitious ventilation in a room (gaps around doors and windows) is assumed to supply the air for the first 7 kW of an open-flued appliance.
How accurate are these figures?
They come from the formulas shown on the page and the stated assumptions (for example a calorific value of 38.7 MJ/m³ for natural gas). The manufacturer’s instructions, the current British Standards and IGEM procedures take precedence. Gas work must be done by a Gas Safe registered engineer.