R1 + R2 calculator

Work out the expected R1 + R2 for a radial or ring final circuit from the cable size and length, or from a Zs and Ze reading, and compare it with your continuity test.

R1 + R2 = length × (line + cpc resistance per metre) ÷ 1000. For 2.5/1.5 mm² twin and earth that is 7.41 + 12.10 = 19.51 mΩ/m, so 20 m gives 0.39 Ω at 20 °C. On a ring final, R1 + R2 at each socket is about (r1 + r2) ÷ 4.

Updated · BS 7671:2018 as amended · check against BS 7671 and your scheme

R1 + R2
0.39 Ω
Resistance of 2.5/1.5 mm² pair at 20 °C
19.51 mΩ/m
Working
  1. 2.5 mm² = 7.41 mΩ/m, 1.5 mm² = 12.10 mΩ/m (copper, 20 °C), so the pair is 19.51 mΩ/m.
  2. R1 + R2 = 20 m × 19.51 mΩ/m ÷ 1000 = 0.39 Ω.

Check before you rely on it: figures are calculated from the formulas and conductor data shown, following BS 7671:2018 as amended. Check critical values against the current edition of BS 7671, the manufacturer’s data and your scheme’s requirements. Competence and compliance remain with the user.

Reference table

R1 + R2 per metre for copper twin and earth at 20 °C (from the maximum conductor resistances in BS EN 60228). Multiply by the length in metres and divide by 1000 for ohms; × 1.20 for 70 °C.
CableLine + cpc (mΩ/m)10 m20 m30 m
1/1 mm²36.200.36 Ω0.72 Ω1.09 Ω
4/1.5 mm²16.710.17 Ω0.33 Ω0.50 Ω
6/2.5 mm²10.490.10 Ω0.21 Ω0.31 Ω
10/4 mm²6.440.06 Ω0.13 Ω0.19 Ω
16/6 mm²4.230.04 Ω0.08 Ω0.13 Ω
1.5/1 mm²30.200.30 Ω0.60 Ω0.91 Ω
2.5/1.5 mm²19.510.20 Ω0.39 Ω0.59 Ω

The formula

Copper conductors have a maximum resistance per metre at 20 °C set by BS EN 60228: 18.1 mΩ/m for 1.0 mm², 12.1 for 1.5 mm², 7.41 for 2.5 mm², 4.61 for 4 mm², 3.08 for 6 mm², 1.83 for 10 mm² and 1.15 for 16 mm². Add the line and cpc values, multiply by the length in metres and divide by 1000 to get ohms.

For design, multiply by 1.20 to allow for a thermoplastic (PVC) cable at its 70 °C operating temperature (1.28 for 90 °C thermosetting cable). For comparing with a test reading, use the 20 °C value.

Ring final circuits

  1. Measure the end-to-end resistance of the line (r1), neutral (rn) and cpc (r2) loops. r1 and rn should be within 0.05 Ω of each other; for 2.5/1.5 mm² cable r2 is about 1.6 to 1.7 × r1.
  2. Cross-connect line and cpc (L1 to E2, L2 to E1) and measure between line and earth at every socket. Each reading should be about (r1 + r2) ÷ 4.
  3. The highest reading is the circuit’s R1 + R2. Readings that rise towards the middle of the ring mean a break or a spur from a spur.

Worked examples

  • Radial, 2.5/1.5 mm², 20 m: 20 × 19.51 ÷ 1000 = 0.39 Ω (0.47 Ω at 70 °C).
  • Ring, 2.5/1.5 mm², 50 m of cable round the ring: r1 = 50 × 7.41 ÷ 1000 = 0.37 Ω, r2 = 50 × 12.1 ÷ 1000 = 0.61 Ω, R1 + R2 = (0.37 + 0.61) ÷ 4 = 0.24 Ω.
  • From a reading: Zs 0.74 Ω and Ze 0.35 Ω give R1 + R2 = 0.39 Ω.

Writing certificates every week? Pro is £39/month ex VAT

  • Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
  • Your logo, company, accreditation and signature on every PDF
  • History with search, copy and re-issue
  • Renewal reminders in the app and in your calendar
  • No “Free version” mark

Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.

See plans

Frequently asked questions

What is R1 and R2?

R1 is the resistance of the line conductor of a circuit, from the distribution board to the furthest point; R2 is the resistance of the circuit protective conductor (cpc) over the same route. Their sum is measured with a low-resistance ohmmeter by linking line and cpc at the board.

Why is R2 bigger than R1 in twin and earth?

The cpc in twin and earth is smaller than the line conductor (for example 1.5 mm² with 2.5 mm²), so its resistance per metre is higher.

What is a good R1 + R2 reading?

One close to the calculated value for the cable size and length, and low enough that Ze + R1 + R2 stays within the maximum Zs for the protective device. A reading much higher than calculated points to a poor connection.

Can I rely on these figures?

They are calculated from the formulas and conductor data stated on the page, and the working is shown so you can check it. They are a design and testing aid, not a substitute for BS 7671:2018 as amended, the manufacturer’s data or your competent person scheme’s requirements. Check critical values against the current edition before you sign anything.