Voltage drop calculator

Enter the cable size, design current and length to get the voltage drop, the percentage of the supply voltage and the smallest cable that keeps you within the limit.

Voltage drop = mV/A/m × current × length ÷ 1000. A 2.5 mm² copper cable is about 17.8 mV/A/m, so 20 A over 30 m drops 10.67 V, or 4.64 % of 230 V: within the 5 % limit for power circuits but over the 3 % limit for lighting.

Updated · BS 7671:2018 as amended · check against BS 7671 and your scheme

✓ 4.64 % is within the 5 % limit.

Voltage drop
10.67 V
Percentage of 230 V
4.64 %
mV/A/m used
17.8
Longest run for 5 %
32 m
Smallest size within 5 %
2.5 mm²
Working
  1. mV/A/m = 2 × 7.41 mΩ/m × 1.20 (70 °C) = 17.78.
  2. Vd = 17.78 × 20 A × 30 m ÷ 1000 = 10.67 V = 4.64 % of 230 V.

Check before you rely on it: figures are calculated from the formulas and conductor data shown, following BS 7671:2018 as amended. Check critical values against the current edition of BS 7671, the manufacturer’s data and your scheme’s requirements. Competence and compliance remain with the user.

Reference table

Approximate voltage drop per amp per metre for copper conductors at 70 °C, worked out from conductor resistance (2 × r × 1.20; three-phase × √3 ÷ 2). Reactance is ignored, which is fine up to about 16 mm².
Sizer at 20 °C (mΩ/m)Single-phase mV/A/mThree-phase mV/A/m
1 mm²18.1043.437.6
1.5 mm²12.1029.025.1
2.5 mm²7.4117.815.4
4 mm²4.6111.19.6
6 mm²3.087.46.4
10 mm²1.834.43.8
16 mm²1.152.82.4
25 mm²0.731.71.5
35 mm²0.521.31.1

The limits

BS 7671 (Section 525 and Appendix 4) treats the voltage drop as acceptable for an installation supplied from a public low-voltage network if it is no more than 3 % for lighting and 5 % for other uses, measured from the origin to the load. That is 6.9 V and 11.5 V at 230 V, or 12 V and 20 V at 400 V three-phase.

How the mV/A/m figure is worked out

For a single-phase circuit the current flows out and back, so the drop per amp per metre is twice the conductor resistance at its operating temperature: 2 × r(20 °C) × 1.20 for a 70 °C thermoplastic cable. For a balanced three-phase circuit multiply by √3 ÷ 2. This calculator works the values out from the BS EN 60228 conductor resistances; they agree with the published tables to within about 2 % up to 16 mm², where reactance is negligible.

Worked examples

  • 2.5 mm², 20 A, 30 m, single-phase: 17.78 × 20 × 30 ÷ 1000 = 10.67 V = 4.64 %. Within 5 %, over 3 %.
  • 6 mm² cooker, 32 A, 25 m: 7.39 × 32 × 25 ÷ 1000 = 5.91 V = 2.57 %.
  • 1.5 mm² lighting, 6 A, 40 m: 29.04 × 6 × 40 ÷ 1000 = 6.97 V = 3.03 %: just over the 3 % lighting limit.

Writing certificates every week? Pro is £39/month ex VAT

  • Every certificate saved: fire alarm, emergency lighting, PAT, EIC, EICR and Minor Works
  • Your logo, company, accreditation and signature on every PDF
  • History with search, copy and re-issue
  • Renewal reminders in the app and in your calendar
  • No “Free version” mark

Business (£79/month ex VAT) adds up to 5 users, a client and site register and bulk reminders. Plans are for businesses (sole traders, partnerships and companies). The forms and calculators stay free.

See plans

Frequently asked questions

Which current should I use?

The design current Ib of the circuit (the current it will carry in normal use), not the rating of the protective device. Where diversity applies to a final circuit, use the diversified current.

Is voltage drop measured from the consumer unit?

From the origin of the installation, usually the supplier’s cut-out. If a sub-main feeds the board, add its voltage drop to the final circuit’s.

Does cable temperature matter?

Yes. The figures here assume the conductor is at its maximum operating temperature (70 °C for PVC), which gives the worst case. A lightly loaded cable runs cooler and drops a little less.

Can I rely on these figures?

They are calculated from the formulas and conductor data stated on the page, and the working is shown so you can check it. They are a design and testing aid, not a substitute for BS 7671:2018 as amended, the manufacturer’s data or your competent person scheme’s requirements. Check critical values against the current edition before you sign anything.